Arc Fault Detection Method Based on CZT Low-Frequency Harmonic Current Analysis
2017
This paper presents a method for the detection of series arc faults in electrical circuits, which has been developed starting from an experimental characterization of the arc fault phenomenon and an arcing current study in several test conditions. Starting from this, the authors have found that is it possible to suitably detect arc faults by means of a high-resolution low-frequency harmonic analysis of current signal, based on chirp zeta transform, and a proper set of indicators. The proposed method effectiveness is shown by means of experimental tests, which were carried in both arcing and nonarcing conditions and in the presence of different loads, chosen according to the UL 1699 standard…
A set of indicators for arc faults detection based on low frequency harmonic analysis
2016
In this paper a novel set of indicators is presented for arc faults detection in electrical circuits. The indicators are defined starting from an experimental characterization of the arc fault phenomenon and the study of the arcing current in several test conditions, which were chosen in accordance with the UL 1699 Standard requirements. The proposed parameters are measured by means of a high resolution low frequency spectral analysis of the arcing current, which allows to achieve a good spectral resolution even with short observation windows.